Ashcroft GC35 - Pressure Sensor Manuel d'utilisateur Page 4

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 4
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 3
4
4. Comparator-Switch / Loop Check Mode: Access by pressing MODE for less
than 3 seconds.
A. Comparator-Switch Setting: To activate / deactivate comparator-switch,
scroll to US1 (4-20mA version only) or US2 and select USE / noU. Enter com-
parator-switch set point by selecting A-1 or A-2 and use #/$ keys for pres-
sure setting. Now enter ‘deadband’ value (pressure difference between set
and reset values) by selecting b-1 or b-2 and use #/$ keys for setting. Note:
unit automatically configures the reset point. Increasing setpoint is entered as
a positive ‘deadband’ value, while decreasing setpoint is entered as a negative
‘deadband’ value.
B. Loop Check: Allows the user to check comparator-switch operation without
requiring pressure input. Use $ or # keys to view comparator-switch function
in a simulated test of the application.
Comparator-Switch Setting / Loop Check Menu
P5I
Function Setting Mode
Filter Setting
Decimal Point Position
Display Unit Setting
Select Comparator Mode
LED Ring Feature Setting
C
omparator Operation
Selection
Measurement Mode
Press 3 sec.
o
r longer
P
ress 3 sec.
or longer
M
ODE
M
ODE
MODE
MODE
MODE
M
ODE
MODE
MODE
MODE
MODE
MODE
MODE
A
fter 1 second
kY5
kY5
!;n
Select with
X W
k
eys
Select with
X W
k
eys
S
elect with
X W
keys
M
essage displayed
Current setting
Hysteresis Window comparator
A
fter 1 second
OP(
npn
npn
pnp
Message displayed
C
urrent unit
setpoint
N
PN output PNP output
S
elect with
X W
keys
EoF
Eon
Power-save OFF Power-save ON
e(O
Message Display Current Setting
e(O
eOf
After 1 second
f;l
f-1
Message displayed
Current setting
After 1 second
lRg
Message Display Current Setting
L
lRI
After 1 second
Select with
X W
keys
ET[
P5I
psi, bar or mPa Display Scaling
UN;
Message Display Current Setting
u
After 1 second
Select with
X W
keys
Power-save setting
(Display Scaling)
Set Offset Value
(Display Scaling Set)
Full Scale Value
Pressure when the
analog is at zero point
Pressure when the
analog is at span point
f-0
Filter off
f-1
Time constant 25ms
f-2
T
ime constant 250ms
f-3
Time constant 2.5s
f-4
Time constant 5s
f-5
T
ime constant 10s
Select with
X W
keys
Set Any Desired Position Within the
–100 to 150% range with the
X W
keys
Set Any Desired Position Within the
–100 to 150% range with the
X W
keys
X W
Key to Select Between
(–)1999~(+)9999
X W
Key to Select Between
(–)1999~(+)9999
0
0.0
0.000
0.00
Lr0
No LED interlock
Lr1
Comparator 1 is
interlocked with LED
Lr3
Comparator 1 & 2 are
interlocked with LED
Lr2
Comparator 2 is
interlocked with LED
d-p
Message Display Current Setting
d
0.00
After 1 second
d-l
Message Display Current Setting
d
0.00
After 1 second
d-K
Message Display
Only in Output Selection
Display Scaling
Current Setting
d
0.00
After 1 second
A-L
Message Display Current Setting
a
0.0
After 1 second
a
Message Display Current Setting
a-k
100.0
After 1 second
D I S P L AY S E T TI N G
A N A L O G O U P U T S CA L IN G
(n~P