!=1.;>7,=287<
*<2,.B89.;*=287<
In all setting modes, values are set with the ▲▼ keys. Use the key to
increase and the key to decrease the value. A repeat state occurs in
three phases of speed when the ▲▼ keys are pressed for more than 0.5
seconds to increase or decrease numerical value. ▲▼ keys are also used
for setting switch, unit and filter in the function setting mode.
-3><=270=1.C.;89827=8/""
In measurement mode, select display to adjust zero using key.
Press + ▲▼ keys for more than 3 seconds (until “---” display
blinks) after releasing pressure from the pressure port. Auto-matic zero
adjustment takes place approximately 1 second later for pressure display
to be zero. When the zero adjustment is successful, is displayed.
Error displays for 1 second when applied presure was outside of
range of –5 to 5% F.S., zero adjustment will not be allowed.
-3><=270=1.C.;89827=8/"
Only when display scaling is selected in display select on function
setting mode, zero adjustment can be done. Press + keys for
more than 3 seconds (until “---” display blinks) after releasing pressure
from the pressure ports. Automatic zero adjustment takes place approxi-
mately 1 second later.