13.2 Setting Items for Linear Display Mode (Re-scaling in arbitrary user
defined units)
Set the filter before setting the linear display mode (Refer to Section
11.1).The following table is the Setting Example 1, Linear Display Mode,
Section 11-3.This applies when re-scaling in arbitrary user defined units.
Setting LCD Setting Setting
No. Item Display Description Range Default*
Display Selection of non:pressure non
mode pressure display display mode
mode : Lin Lin:Linear display
mode
Minimum Min. pressure Pressure range 0.0
pressure corresponding to 0 to 75%F.S.
OFFSET 9
: 10 (psi)
Maximum Max. pressure Pressure range 100.0
pressure corresponding to 25 to 100%F.S.
FULL SCALE 10
: 60 (psi)
Decimal Display after 0,1,2,3 digit 0
point decimal point
position Number of digits
: 2 (digit)
OFFSET OFFSET –1999 to 1999 0
corresponding to
min. pressure 6
: 0.00 (ton)
FULL FULL SCALE –1999 to 1999 1000
SCALE corresponding to
mAX. pressure 7
: 5.00 (ton)
Output Analog output Maximum display 0.0
zero point†† zero point (4mA) span: –10
: 0.0 (%F.S.) to 110%F.S.
Output Analog output Maximum display 100.0
span point†† span point (20mA) span: –10
: 100.0 (%F.S.) to 110%F.S.
Loop Arbitrary change of Display: linear 0.00
check‡ linear display and display (4.0mA)
analog output Analog output
: 5.00 (ton) 4 to 20mA
n L;n
d 0.00
d 5.00
d 2
p 60.0
[ 5.00
a 100.0
a 0.0
p 10.0
-