Setting of integrated volume
When a momentary flow rate unit is set as an arbitrary unit, the
integrated volume is also an arbitrary unit and the factor of the
two following points must be set:
• Setting of time factor (second, minute, hour)
• Setting of flow factor weight (1, 10, 100, 1000)
In the differential flow meter whose differential pressure generated
at maximum momentary flow rate of 1.000L/s is 16IW (80%F.S.)
and which uses a differential pressure range of 0 to 2.0 IW, the
setting of momentary flow rate of arbitrary unit and the setting of
integrated volume of the arbitrary unit (in order to display 1 per
count) are as follows: In this case, the low-cut is set as 10%F.S.
and the display switching method is set as manual.
Select the “Square root display mode” ==> Setting item
Set the differential pressure at max. momen-
tary flow rate as 16IW (80%F.S.) ==> Setting item
Select “3-digit” as decimal point position
of momentary flow rate ==> Setting item
Set the max. momentary flow rate as “1.000.” ==> Setting item
Set the low-cut as “10.0%F.S.” of max.
display span* ==> Setting item
Set the output zero point as “0.0%F.S.”
0 of max. display span* ==> Setting item
Set the output span point as “100.0%F.S.”
1 of max. display span* ==> Setting item
Select “SEC” (second) as time factor of
integrated volume ==> Setting item
Select “1” as weight of flow factor of
integrated volume ==> Setting item
21
Select “bt” (manual) as display
switching method ==> Setting item
22
*Maximum display span: 0 to Maximum momentary flow rate